Why does the compressiong filter out a valuable data?

$
0
0
7:08:30 AM 107.5667 7:08:35 AM 90.15 7:08:39 AM 79.32 7:08:45 AM 0 8:30:25 AM 91.1 8:30:30 AM 106.25 8:30:46 AM 119.2

 

 The data above are collected with compressed data function of Datalink. The tag is an amps of a motor. As you see above, the motor stops at 7:08:45 and starts back up 8:30:25. But since we set 'step attribute' off, there is an interpolated line between these two dots. Why does not PI record the prior event to 8:30:25?

 

Below are the setting of the tag in SMT:

typical value:100  zeo:0   span:200

Scan: On   Archiving: On    Step: Off   Shutdown: On    Compression: On

Exception Dev: 1 Eng. Units  Compression Dev: 2 Eng. Units

ExpMin: 0  ExpMax:10mins   CompMin: 0  CompMax: 8hrs

 

Thanks